Eaton Blade UPS - Technical Specifications :
Product Snapshot
Power Rating: 12-60 kW
voltage: 400V
Frequency: 50/60 Hz
Configuration: Rackmount
Product Series: Eaton
UPS Models
Eaton BladeUPS Power System Technical Specs
General Characteristics
Power Rating : 12 kW per UPS Module
Efficiency : Up to 97%
Heat Dissipation : 371W/1266 BTU/hr. at 100% rated load
Cooling: Fan cooled, temperature microprocessor monitored; front air entry, rear exhaust
Audible Noise, Normal Operation <60 dBA at 1 meter
Altitude before derating 1000 meters (3300 ft. ASL)
Input Characteristics
Input Voltage: 208 Vac and 400 Vac models
Voltage Range : 208V model: 180 to 265 Vac
400V model: 311 to 519 Vac
Frequency Range 50 or 60 Hz, ±5 Hz
Input Current Distortion: <5% with IT loads (PFC power supplies)
Input Power Factor:>0.99 with IT loads (PFC power supplies)
Inrush Current: Load dependent
Input Requirements: Three-phase, four-wire + ground
Bypass Source: Same as input, (single feed)
Generator Compatibility :Fast sync slew rate for optimum generator operation
Output Characteristics
Rated Output Voltage 208V model: 180 to 225 Vac, Ph to Ph
400V model: 180 to 240 Vac, Ph to N
Output Configuration Three-phase, four wire + ground
Output Frequency (nominal) 50 or 60 Hz auto-detection on startup
Frequency Regulation 0.1 Hz free running
Load Power Factor Range Lagging: 0.7
Leading: 0.9
Total Output
Voltage Distortion : <3% with IT loads (PFC power supplies)
<5% non-linear or non-PFC power supplies
Battery Characteristics
Battery Type VRLA - AGM
Battery Runtime (Internal) 13 minutes at 50% load
4.8 minutes at 100% load
Battery String: Voltage 240 Vdc
Battery Test :Automatic battery test standard (remote scheduling capable).
Manual battery test from front display
Battery Recharge Profile ABM three-stage charging technology
Battery Cut-off Voltage Variable from 1.67 VPC at <5 min. runtime to 1.75 VPC at >90 min. runtime
Battery Low Condition Announced with alarm
Extended Battery Capability Yes, add up to four additional 3U battery enclosures
(~34 min at 100% load, >1 hour at 50% load)
Physical Characteristics
Dimensions H x W x D, in (mm)
UPS
EBM 10.3 (6U) x 17.4 x 26.0 (267 x 442 x 660)
5.2 (3U) x 17.2 x 26 (132 x 437 x 660)
Note:
Total Chassis Weight without batteries or electronics
Total Chassis Weight with batteries or electronics 46 kg
140 kg
Total UPS Weight without Batteries 61 kg
Total UPS Weight with Batteries 140 kg
EBM Weight 77 kg
Communications and User Interface
Software Compatibility UPS ships with Software Suite CD containing LanSafe power management software
X-Slot Bays Two available for the cards listed below
Control panel LCD Two lines by 20 characters
Four menu-driven interface buttons
Four status at a glance LEDs
Multi Language English standard; 20 languages available
Configuration Changes User capable, firmware auto configures.
Dry Contact Inputs Two, user configurable
Dry Contact Outputs One, user configurable
Certifications
Safety 208V model: UL1778, cUL
400V model: CE
EMI 208V model: FCC Part 15 Class A
400V model: EN62040-2 Class A
Surge Protection ANSI C62.41, Cat B-3
Hazardous materials (RoHS) EU Directive 2002/95/EC Category 3 (4 of 5)
Warranty
Standard 12 months
Options and Accessories : Detachable input cord
Detachable input/output cord assembly
Detachable paralleling cord assembly
Extended Battery Modules (EBM)
3U output sub-distribution modules (RPM)
0U to 3U rack power strips
60 kW BladeUPS Parallel bar
Four-post rail kit
Optional X-Slot Communication Cards
Application:
Web SNMP: ConnectUPS-X Web/SNMP Card
Modbus RTU: Modbus Card
Environment Monitoring: EMP Environmental Monitoring Probe (requires Web/SNMP card)
IBM eServer™ (i5™, iSeries™,or AS/400), industrial: Relay Interface Card
Parallel: Powerware Hot Sync Card
CAN Bridge card
Remote LCD Display: ViewUPS-X
Recommended ePDU
Y032440CD100000 RPM - Rack Power Module (BladeUPS in, 12xC13 + 6xC19 out) 20 ft lead
PW107BA0UC08 :ePDU - Basic (0U, Dual 16A C20 in, 24xC13+ 8xC19 out) use in addition to RPM
PW107MI0UC08 :ePDU - IP Monitored (0U, Dual 16A C20 in, 24xC13+ 8xC19 out) use in addition to RPM
PowerRatings : 15kVA/13.5kW, 20kVA/18kW, 30kVA/27kW, 40kVA/36kW, 60kVA/54kW, 80kVA/72kW, 100kVA/90kW, 120kVA/108kW, 16... Continue
We acquire expertise in manufacturing and supplying wide range of items. Here our firm is providing Eaton 9E-IN to our c... Continue