Power
Ratings : 15kVA/13.5kW, 20kVA/18kW, 30kVA/27kW, 40kVA/36kW, 60kVA/54kW, 80kVA/72kW, 100kVA/90kW, 120kVA/108kW, 160kVA/144kW, 200kVA/180kW, 300kVA/270kW, 400kVA/360kW, 500kVA/450kW
Topology: double-conversion online UPS
Electrical Input
Nominal input voltage: 400/230V, 4 wire (380/415V selectable)
Input voltage range :-15%, +20% from nominal (400V) at 100% load without depleting battery
Operating frequency : 50/60 Hz (40 to 72 Hz)
Input power factor : >0.99 typical
Input current distortion : ≤5% THD
Electrical Output
Nominal output voltage : 400/230, 4 wire (380/415V selectable)
Output voltage regulation :+1% Static; +5% dynamic at 100% resistive load change, <20 ms response tim
Battery
Battery: 192 to 240 Cells (Continual selectable for 15-80kVA)
216/222/228/234/240 Cells (Selectable for 100-500kVA)
Charging method: ABM Cyclic Charging
General
Efficiency : > 98% High-efficiency mode (15-80kVA)
> 98.5% High-efficiency mode (100-300kVA)
> 99% High-efficiency mode (400-500kVA)
> 94% Double conversion mode (15-300kVA)
> 96% Double conversion mode (400-500kVA)
UPS bypass : Automatic on overload or UPS failure
Parallel technology : Powerware Hot Sync® Technology
Dimensions W x D x H : 500 x 710 x 960 (mm) 15-20kVA (with internal battery)
500 x 710 x 1230 (mm) 30kVA (with internal battery)
500 x 710 x 1500 (mm) 40kVA (with internal battery)
600 x 800 x 1876 (mm) 60-200kVA
1600 x 820 x 1880 (mm) 300/400/500k
Cabinet rating : IP20 with standard washable dust filters
Weights without internal battery :15/20kVA-72kg, 30kVA-88kg, 40kVA-120kg,
60kVA-202kg, 80kVA-245kg, 100kVA-283kg,
120kVA-311kg, 160/200kVA-457kg,
300kVA-860kg, 400kVA-970kg, 500kVA-1020kg
Weights with internal battery : 15/20kVA-272kg, 30kVA-376kg, 40kVA-490kg
Overload :150% for 1 minute, 125% for 10 minutes, >150% for 150ms
Environmental
Operating temperature : 0oC to +40oC
Batteries recommended max. +25ºC
Storage temperature : -25oC to +55oC without batteries
+15oC to +25oC with batteries
Relative humidity :5–95%, non-condensing
Audible noise :15-20kVA<55 dBA at 1m typical
30-40kVA <62 dBA at 1m typical
60-120kVA <65 dBA at 1m typical
160-200kVA <70 dBA at 1m typical
300-400kVA <73 dBA at 1m typical
400-500kVA ≤75 dBA at 1m typical
Altitude : <1000m at +40°C
Certifications
EMI standards: EN55022/EN55024
EMC compliance : IEC 62040-2
Quality: ISO 9001: 2000 and ISO 14001:1996
Communication Accessories
Network-MS :Web/SNMP Card
Modbus-MS : Web/SNMP and Modbus Card
Relay-MS : Relay (Dry Contact) Card -DB9 Connection
Industrial Relay: Relay (Dry Contact) Card -Terminal Connection
116750224-001: Environmental Monitor Probe (EMP) kit (need to plug into Web/SNMP Card or Web/SNMP and Modbus Card to work)
System Accessories: Battery Cabinets & Battery Circuit Breakers (60-200kVA)
Maintenance Bypass Switches (MBS) (100-200kVA, standard on 15-80kVA)
Top Cable Entry (60-200kVA, standard on 300-500kVA)
System Parallel Modules (60-200kVA)
Dual input kit (15-80kVA)
IP21 hood (15-200kVA)
Rear Chimney (60-200kVA)
We acquire expertise in manufacturing and supplying wide range of items. Here our firm is providing Eaton 9E-IN to our c... Continue
Eaton Blade UPS - Technical Specifications :Product SnapshotPower Rating: 12-60 kWvoltage: 400VFrequency: 50/60 HzCo... Continue